
IT
has been said, that the heart of any home is the fire place. Not surprisingly,
as through the ages the food was cooked ,water heated and being the only source
of heat to ward of the inclement elements became the centre of the household.
Fire
places in days gone by were little more than a fire lit on the bare earth,
supplying heat for
the one communal room. The smoke from the fire raising up undirected
through the badly constructed thatched roof. The only control, was by the amount
of fuel added to the fire. As you can imagine ,with the room being full of smoke
and the thatched roof becoming
saturated with tar deposits there could not have been a more unpleasant
not to mention an unhealthy place to live.
When
need arouse to add a first floor to these dwellings, there was obviously a need
to direct the smoke from the fire burning on the ground floor up and out through
the roof ,thus the first chimneys were constructed. These being little more than
a construction of a large ingle
nook to catch the smoke, tapering in size as it past through the first floor and
thatched roof.
This
being a great improvement, as not only was the smoke directed out off the
building, but the heat stored in the building fabric of the chimney heated the
upper floor. It was also found that as the chimney heated up the velocity of the
smoke in the chimney increased allowing the fire to burn more vigorously.
Many
of this type of chimney in some form survive today.
Problems you could experience and how to solve them.
There is nothing more frustrating, having just
altered or installed a new fireplace or stove, than to find it SMOKES back into
the room. The local builder immediately fits a cowl, which often does nothing to
help, or makes things worse!
Problems associated with chimneys can be broadly
divided into 3 main types:
1) Poor flue pull and the emission of fumes or
smoke into the room where the fire/appliance is situated.
2) Leakage of smoke and fumes from the flue into
adjoining rooms or roof spaces.
3) Ingress of water/dampness due to entry of rain
into the flue or condensation from the flue gases.
it is important to understand how a flue works. A flue is basically a column of hot air and gases, which is lighter than an equivalent column of cold air outside. Observe a bonfire on a still day. The smoke naturally gathers in a column rising vertically above the fire. But once it cools to the temperature of the surrounding air it rapidly slows
Take note of the following
1) Smoke wants to rise
vertically, therefore any bends or sloping sections in a flue are going to slow
down the flow and hence the clearance of smoke from the fireplace.
RULE - Flues should ideally be
vertical. If an offset is necessary, it should be as near vertical in angle as
possible. 30 degrees from the vertical is the recommended maximum. 45 degrees
bends are really too steep, although permitted in some circumstances.
2) The smoke only rises as long
as it is warmer than the surrounding air. The greater the temperature difference,
the faster it will raise.
Main course of a smoke being emitted into
the room
1. The Ratio Problem
|
The
FIREPLACE OPENING is too large for size of FLUE, i.e. the volume and speed
of the smoke passing up the flue is insufficient to clear the large volume
of fumes building up in the oversize fireplace opening below. Flues above
6m tall should generally be not less than 1/7th to 1/8th of the area of
the fireplace opening, e.g. a 225 mm (9") diameter flue will support
a fireplace opening up to about 550 x 550 mm (22" x 22") (see
Building Regulations J 2.2.) For bungalows, the ratio should be reduced to
1/6th |
|
As it is
generally impractical to consider rebuilding the flue to a larger size, the
fireplace opening must be reduced. There are a number of ways this may be done,
depending on the size of the original fire opening and the purpose for which the
fire is intended.
For larger
fireplaces and inglenooks, the whole flue should be closed off with a horizontal
register plate just above beam or lintel height. A freestanding fire, bricked-in
convector open fire, closed stove, or canopy can then be fitted with a flue
projecting through the register plate. An access trap must be provided for
cleaning above the register plate. (See leaflet 1 OPEN FIRES D.1)
For smaller
fire openings (up to say 900 mm (3') square, a smoke hood, canopy or tempered
plate glass strip, can be fitted across the full width of the fire opening,
effectively lowering the height of the lintel. It is best to experiment first,
using a strip of sheet metal, fireproof board or even hardboard pinned or wedged
in position. (Do not leave the fire unattended if hardboard is used.) This can
be lowered until the fire no longer smokes before making a permanent job. Try
the experiment for a couple of weeks before finally accepting success.
A raised
plinth can also be built to reduce the opening size. This can be temporarily
built from old bricks built loose and jointed with dry sand. (See diagram 1.)
Installing a convector firebox is also a good solution in this situation.
2. The Air Starvation Problem
or lack of room ventilation.
All fires must have oxygen to
burn. Air contains approximately 20% oxygen, therefore five times as much air is
needed than the oxygen required for proper combustion. Additionally, open fires
also take considerable quantities of air to vent the smoke up the chimney.
Modern homes tend to have solid
tight fitting doors and draught stripped windows. Lack of ventilation to the
room is therefore a common cause of smokiness, more particularly in modern or
modernized homes.
Trying to burn either solid
fuel or gas with insufficient ventilation will have two effects:
If insufficient oxygen is
available to the fire, incomplete combustion will take place. In simple
terms, the products of complete combustion are carbon dioxide and water vapour.
Lack of oxygen however will produce carbon monoxide, an odourless and
highly poisonous gas.
Secondly, lack of ventilation
will mean insufficient air is available to replace that being drawn up the flue
and needed to clear the smoke and fumes from the fire. Result, smoke or spillage
of the fumes, including the carbon monoxide, into the room.
THIS
IS A VERY DANGEROUS SITUATION.
If the fire works well when the
room door is open, but smokes when the door is shut, the problem is air
starvation. This is not a fault in the construction of the fireplace or flue,
but a lack of room ventilation. Ventilation requirements are laid down in the
Building Regulations.
To cure this problem,
additional air must be brought into the room, preferably without introducing
unacceptable cold draughts. Either vent directly through an outside wall, or
vent into the hall (or a conservatory) and then to outside. If the fire works
well with the door to the hall open, this has proved that there is sufficient
ventilation from the main house. Also, a vent from the hall to outside is
usually more acceptable than a vent from the living room direct to outside. If
the room has a suspended wood floor with air bricks round the outside of the
house, then a simple floor grille cut into the floorboards to one side of the
hearth or chimney breast is a good solution. Grilles must have a sufficient free
open area. Aim for half the cross section of the flue as a minimum. Do not vent
air up immediately in front of the fire opening.
3. Badly sited chimney
terminal
The best place for a chimney to
terminate is on or near the roof ridge, and well above it.
Two distinct problems can occur
with a badly sited chimney terminal, although the symptoms can be similar.
|
i) Down
draught (See diagram 2) In this situation, wind
blowing over another tall building, tree or hill, descends onto the
chimney top, causing a puff of smoke or fumes in the room, usually
intermittently. |
|
|
|
ii) Pressure
Zone (See diagram 3) Here the chimney is sited
in the line of the prevailing wind, with a taller object, house, roof, and
tree or nearby hill behind the chimney terminal. This can cause puffing or
continuous fume emission when the wind is blowing. |
|
For
downdraught problems, certain types of cowl can reduce the problem, or
construct a slab top or dovecote top (see diagram 4).
Pressure zone problems
are more difficult to deal with. The best solution is to raise the chimney
until it is above the pressure zone. This can be done experimentally by
fixing a length of single skin metal pipe over the existing pot. If this
works, a tall chimney pot can be installed. (Tall pots are made up to 1500
mm (5') high. Alternatively,
if the |
|
chimney is much too low, a
combination of a tall pot plus raising the stack 600-900 mm (2'-3') may be
necessary. Note: Building Regulations A 1/2 D gives maximum height for a chimney
stack, including pot, as 411, times the narrowest width, measured from the
highest point where it leaves the roof. Cowls rarely do much good in pressure
zone situations. The MARCONE chimney pot can be useful to increase
chimney height and help to counter down draught. (See diagram 4).
It may also help to introduce
some room ventilation on the same side as the prevailing wind, helping to
equalize the pressure at the top and bottom of the chimney. Try opening a small
window on the windward side of the house. If this helps, fit a permanent air
vent.
If all else fails, an electric
chimney fan may be the only solution.
1. Badly formed throat or gather
The throat or back of the
lintel should slope upwards at 45 degrees into the flue. Often a standard
concrete lintel is used across the fire opening forming a flat soffit above the
fire. Add to this a stone fireplace surround with a course of stone in front of
this lintel and the smoke will strike this flat area and trickle out into the
room. Also the gather above the fireplace is sometimes of rough brick or stone
and will severely restrict the smoke reaching the flue. Either this lintel must
be replaced or, possibly, a sloping metal smoke hood will help.
2. Partially blocked flue
With older chimneys, a large
piece of the mortar lining may fall across, or a brick or piece of stone from
the upper dividing masonry to a neighbouring flue may collapse, partially
blocking the flue. This obstruction may sometimes be dislodged with sweep's
rods. Otherwise it will be necessary to open up the flue to clear the blockage.
It may be necessary to line the flue.
In modern flues constructed
with clay liners, mortar squeezed from joints are often not properly cleaned off
during construction. Particularly if 45 degree bends are used to form an offset,
mortar droppings can be left on the bend, partially obstructing the flue. These
can be difficult to remove and may also require opening the flue to clear.
Tar build-up can also
partially, or even wholly, block a flue. If wood is burned, and a smoke problem
has gradually got worse, this is a likely cause. The blockage is usually near
the top of the chimney where the gases are cooling. If tar is forming in a tall
pot, replace this with a shorter one with, say only 150 mm (6") projection.
Sweep's rods and a scraper or steel wire brush may dislodge some tar. However,
it is often baked on like hard pitch and may be difficult to remove. In extreme
cases the chimney will need to be opened to clear these deposits. Chemical
chimney cleaners may help to loosen tar deposits if used over a period of weeks
with frequent sweepings. Professional advice
should be sought concerning the suitability of chemical cleaners, as some can be
harmful to certain flue materials. There are specialist contractors who can ream
out obstructed flues.
If wood is being burned,
IT MUST BE DRY AND SEASONED.
3. Incorrect chimney terminal
Many chimney pot designs and
add-on cowls are far too restrictive when compared to the size of the flue. The
best terminal for most chimneys is a plain, straight-sided pot of the same size
as the flue. Also, many pots are fitted onto older flues by placing a piece of
slate across each corner of the flue. If this is done carelessly, an obstruction
can be formed inside the base of the pot, on which soot and tar can build up
4. Sharp bends and long
offsets
In older flues, offsets were
usually formed at small angles from the vertical by corbelling brickwork across.
However in some larger homes, flues were all carried over to a large central
chimneystack, often involving long near horizontal runs of flue. These will tend
to give trouble and block with soot and debris. It is often necessary to install
additional tight-fitting soot door access points in such flues.
|
In
modern house construction using clay liners, sharp offsets are often
created using two 45-degree clay bends in the mistaken belief that this
makes a flue draw. This sharp offset then easily blocks with a few sticks
from an enthusiastic jackdaw, or soot and tar build up. In extreme cases
it may be necessary to open a section of wall and rebuild a gentler
offset. Horizontal sections of flue pipe are sometimes used to connect a
stove to a chimney. Any horizontal connection should be no longer than
150mm (6"). (Building Regulations J 1.19).If a thick wall has to be
penetrated, this must be done at no less than 45 degrees (See diagram 5). |
|
5. Flue is too large
If a flue is very large, then
the flue gases will cool quickly as they enter it, thus reducing the up draught
and spilling back into the room. This particularly occurs with inglenooks. The
best solution is to extend the neck of the canopy or flue pipe from the
appliance well up inside the chimney above the register plate. Adding 2m (6')
will often cure the problem. It is, however, better to have a flue a little
oversize than undersize. An access door must be provided for cleaning above a
register plate. Alternatively, line the whole chimney with a liner sized to suit
the type of fire being used.
6. Flue is too tall
With a very tall chimney, the
flue gases will often cool so much before they reach the terminal that a cold
plug of air is left at the top of the flue and acts like a cork. This can occur
when first lighting the fire and later in the evening when the fire has died
down. Try keeping a hotter fire burning, or fit an appliance with doors, which
can be warmed up more quickly than an open fire. It may be necessary to install
an insulated liner in some cases. Seek professional advice first.
7. Leaky Flue
If the mortar joints are open
in an old flue on an outside wall, or in the chimneystack above the roof, cold
air can be drawn or blown into the flue. This has two effects-- it cools the hot
rising gases, reducing the up draught, and causes turbulence in the flue, both
of which can lead to smokiness. Re-pointing or rendering can often help.
Alternatively it is often best to line the flue.
8. Collapsed mid-feathers
In old chimneys, the flues in
the stack were often divided from each other by building bricks 'on edge' or
slates or thin pieces of stone between the flues and not bonding them into the
outer walls of the stack. With time and corrosion from the smoke, a section of
these "mid-feathers" or "withes" collapse. This may cause
blockage of a flue that is in use (see (2) above) or fall down a disused bedroom
flue. The effects of these missing mid feathers can be similar to (7) above,
causing cross draughts and eddies in the rising flue gases. This problem can
often be identified if smoke is observed rising from 2 or more of the chimney
pots. The solution is either to rebuild the stack or have the flue in use lined.
(See diagram 6.)
9. Siphonage
This problem is best understood
by looking at diagram 6. It can occur when two flue outlets are close together,
the wind blowing the smoke from one flue directly across the outlet of another.
It can also occur when the mid feathers have collapsed inside the
|
chimney
or there are open joints linking two flues together. (See (7) above).
There are three possible solutions:
i) Fit a taller pot to
the working flue. ii) Line the chimney if
the leakage is inside the stack. iii) Improve the
ventilation in the room where the fire is. ã
D S Hinds 1997 |
|